Bright red fire rated roller shutters closed across a commercial corridor opening.

What Are Fire-Rated Roller Shutters and Where Are They Required?

Fire rated roller shutters stop fire and smoke spreading through commercial buildings. Learn how fire shutters work, where the regulations require them and how to keep them compliant.

Fire rated roller shutters help stop fire and smoke spreading through commercial buildings.

In many premises, they also protect escape routes, stock and neighbouring units.

At Kinetic Door Systems, we supply, install and service fire rated roller shutters across the UK.

In this guide, we explain what fire shutters are, how they work and where the law requires them.

What Are Fire Rated Roller Shutters?

Fire rated roller shutters are steel shutters that close automatically when a fire starts.

Once closed, they hold back flames and heat for a set period, often 60 to 240 minutes.

Unlike standard roller shutters, manufacturers test them to strict fire resistance standards.

As a result, they form part of a building’s fire compartmentation strategy.

Put simply, they keep a fire in one zone while people leave safely.

How Do Fire Shutters Work?

During normal use, fire shutters stay open or work like everyday commercial roller shutters.

When the alarm sounds, however, the shutter descends under control and seals the opening.

Most systems close in one of these ways:

  • Fire alarm link: the alarm panel sends a signal that triggers closure.
  • Fusible link: a heat-sensitive link melts and releases the curtain.
  • Smoke detectors: local detectors spot smoke and start the descent.
  • Gravity fail-safe: the shutter still drops if mains power fails.

In addition, a governor controls the closing speed so the curtain does not slam down.

Where Are Fire Rated Roller Shutters Required?

Building Regulations and fire risk assessments decide where a building needs fire rated roller shutters.

Typically, you will find them in these locations:

  • Compartment walls: openings that pass through fire-resisting walls between zones.
  • Kitchens and serveries: counter shutters in schools, hospitals and canteens.
  • Warehouses: openings between storage areas, offices and loading bays.
  • Shopping centres: shop fronts that open onto shared malls and escape routes.
  • Plant and boiler rooms: high-risk areas that need extra protection.
  • Multi-occupancy buildings: openings between separate tenants or units.

Above all, any opening in a fire-resisting wall needs protection to the same rating as the wall.

Fire Shutter Regulations and BS 8524

Several rules and standards cover fire shutter regulations in the UK.

Approved Document B

Approved Document B sets out fire safety guidance under the Building Regulations.

Specifically, it explains compartmentation and how designers must protect openings.

BS 8524

BS 8524 covers active fire curtain barrier assemblies, which work alongside shutters in many buildings.

Meanwhile, testing bodies assess fire shutters to BS 476 or BS EN 1634-1.

The Regulatory Reform (Fire Safety) Order 2005

Under this order, the responsible person must keep fire safety equipment in good working order.

Therefore, building owners need regular inspections and a clear maintenance record.

Fire Shutters vs Fire Doors

Both fire shutters and fire doors protect openings, but they suit different jobs.

Fire doors work best for people and everyday pedestrian routes.

By contrast, fire rated roller shutters cover wide openings such as loading areas and counters.

Consequently, many buildings use both types within one fire strategy.

Maintenance and Annual Inspections

A fire shutter only works if it closes correctly on the day of a fire.

For that reason, a competent engineer should test and service it at least once a year.

  • Drop tests: confirm the curtain closes fully and at a safe speed.
  • Alarm checks: make sure the shutter responds to the fire panel.
  • Battery and power checks: test back-up units and fail-safe release.
  • Curtain and guides: look for damage, wear or obstructions.
  • Records: log every service to show compliance.

Likewise, staff should keep the area under the shutter clear at all times.

Choosing the Right Fire Rated Roller Shutter

Before you choose, think about these points:

  • Fire rating: match the shutter to the wall’s fire resistance period.
  • Size: measure the opening and the headroom above it.
  • Operation: decide between manual, electric or counter shutters.
  • Certification: ask for third-party test evidence and installer certificates.

Ultimately, a professional site survey ensures the right fit for your building.

Our Door and Shutter Services

Alongside fire shutters, Kinetic Door Systems offers a full range of commercial door services:

Want to see the quality of our work first? View our gallery of completed projects.

Alternatively, get in touch today to discuss fire protection for your site.

Frequently Asked Questions About Fire Rated Roller Shutters


Q1: How long do fire rated roller shutters last in a fire?

A1: Most models offer between 60 and 240 minutes of fire resistance.

Therefore, choose a rating that matches the wall around the opening.


Q2: Do fire shutters need annual inspections?

A2: Yes, a competent engineer should inspect and test them at least once a year.

Busy sites may also benefit from six-monthly checks.


Q3: Can fire shutters work without power?

A3: Yes, most fire shutters include a fail-safe gravity release.

In other words, the curtain still closes if mains power fails.


Q4: Are fire shutters the same as fire doors?

A4: No, fire doors suit pedestrian routes, whereas fire shutters cover wider openings.

Even so, both protect compartments within the same fire strategy.


Q5: Who is responsible for fire shutter maintenance?

A5: The responsible person under the Fire Safety Order holds this duty.

Usually, that means the building owner, employer or managing agent.


Protect Your Building with Fire Rated Roller Shutters

In short, fire rated roller shutters contain fire, protect escape routes and support compliance.

Better still, our team can survey, install and maintain them for you.

To discuss fire rated roller shutters for your premises, enquire now for a free, no-obligation quote.

For more expert advice on doors and shutters, explore our latest insights.

Kinetic Door Systems LTD

Whether you need door installation for your business or home we are here to help with bespoke solutions that won’t break the bank.